HT Switchgear (LBS/VCB)
HT Switchgear (LBS/VCB)
1No emergency trip push button (mechanical). Mimic: A single line diagram showing the direction of power flow shall be dawn on the front of load break switch. The mechanical operation of switch shall automatically indicate ON/OFF status of both main switch as well as the earth switch in the mimic diagram. Fluorescent lamps for sufficient illumination shall be provided.
CURRENT TRANSFORMER
Type : Resin cast, bar primary.
Ratio, burden accuracy class, cores : 50/25/5/5A, 15VA, class 1.0formetering. 5P15for Protection for transformer feeder.
Short time rating : current 18.4 KA for 3sec
Dynamic stability : 47KA peak
Insulation level
a} Impulse with stand voltage : 75 KV PEAK
- b) PF with stand voltage : 28KV (RMS)
Thermal over load capacity : 120%continuous
Applicable standard : MPE-2021
POTENTIAL TRANSFORMER:
Type : Resin cast. Natural air cooled
Ratio : 11KV/3, 110V/3
Rated burden : 20VAIPhase.class1.0
Connection : Three single phase PT with suitable power pack for DC Shunt trip
Voltage : factor 11continuous, 1.5 for 30 sec
INSULATION LEVEL
Impulse with stand voltage : 75KV (P)
PF with stand voltage : 28KVRMS
Protection : HV side 2Amp.HT HRC fuse for each phase
Applicable standard : MPE-2021
INDICATING METERS
Type of meters : Ammeters. Voltmeters
Type of movement : Taut band
Size : 96x96mm
Dial finish : White painted dial with pointer type needle
Mounting : Flush mounting’
Accuracy Class : 1.0
Voltage / current : 110 V PT.5A CT sec current
Applicable standard : MPE-2021
INDICATING LMPS:
VCB ON/OFF/AUTO TRIP/Trip Circuit Healthy/Spring Charged indication lamps
LBS ON/OFF Indication lamp
RYB Indication Lamps
Indication lamps shall be complete with lens cover sand holders
Each lamp shall be fitted with a durable resistance integrally wired in series within the lamp.
The lamp cover (lens) shall be translucent of red color.
Bulbs and covers shall be inter changeable easily replaceable from the front without the need for any special means.
Terminals having potential above 120V shall be shrouded to prevent. Contact with personnel.